Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM00885
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/28/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/28/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Heating and cooling load calculations not included with submittal. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.] 2. Mechanical details 101, 109, and 110 show the fan coils and ERV units suspended from the structure above with spring isolators. The structural detail 31/S1.3 shows the units sitting on structural members without vibration isolation. Coordinate the details. [Initial comment: Coordinate the support of the fan coil and energy recovery units with the structural details. Reference: Section 302.1, IMC 2012.] 3. Show the exhaust flow rate for the chemical hood exhaust. [Initial comment: Show the exhaust flow rates for the chemical and biological fume hoods. Reference: Section 501.4, IMC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/08/2014 | SHANAE POWELL | REJECT SHELF | Completed |