Permit Number: T14CM00128
Parcel: 117031460

Address:
820 N PERRY AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM00128
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 2-06-14
Activity: T14CM00128
Address: 820, 822 N Perry Av
Applicant: Maurice C. Brown

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use.

FLOOR PLAN:
2. Provide sufficient emergency escape/rescue openings from sleeping rooms, R310. Minimum clear opening = 24" high x 20" wide.

PLUMBING PLAN:
3. Include clothes washing machines on water supply fixture schedule.
4. The Tucson Water policy adopted 7/13/12 limits the maximum demand for a 5/8" water meter to 15 GPM. Provide minimum ¾" water meter for the proposed water supply demand, Reference Tables P2903.6 and P2903.6 (1), IRC 2012.

MECHANICAL PLAN:
5. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
6. All outlets specified in section E3902.12 shall be protected with combination-type arc-fault breakers (including existing branch circuits that are extended).
7. Specify faceplate grounding per E4001.11.1.
8. Specify tamper resistant receptacles per E4002.14.
9. Kitchens require two or more 2O-amp small appliance circuits to serve countertop receptacles. Such circuits shall be GFCI protected and shall not serve other rooms (except breakfast areas, pantries, etc.), E3901.3.
10. Convenience receptacles and light switches/fixtures shall be provided within 25' of mechanical equipment, E3901.12, E3903.4.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2014 CPIERCE1 REJECT SHELF Completed