Permit Number: T13CM07532
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM07532
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.0 (FOUNDATION KEYNOTES); DETAIL 101: KEYNOTE 2 INDICATES A NEW COLUMN WITH AN ATTACHMENT TO THE EXISTING POST OF A 1/4" X 1/2" LONG FILLET WELD AT 12" O.C., WHILE DETAIL 101 INDICATES A 1/4" X 1 1/2" LONG FILLET WELD AT 12" O.C. CLARIFY.
2. SHEET S2.0 (DETAIL 101); STRUCTURAL CALCULATIONS (SHEET 1): THE CALCULATIONS INDICATE A GRADE BEAM 2'-6" WIDE X 5'-0" DEEP, WHILE THE DETAIL INDICATES A 1'-4" WIDE X 2'-0" DEEP FOUNDATION WALL WITH A 3'-6" WIDE X 1'-6" DEEP FOOTING. CLARIFY.
3. SHEET S2.0 (DETAIL 102); STRUCTURAL CALCULATIONS (SHEET 1): THE CALCULATIONS INDICATE A 3'-0" DIAMETER CAISSON, WHILE THE DETAIL INDICATES A 3'-6" DIAMETER. CLARIFY.
4. SHEET S2.0 (DETAIL 102); STRUCTURAL CALCULATIONS (SHEET 1): THE CALCULATIONS INDICATE A HSS8X8X1/4 POST, WHILE THE DETAIL INDICATES A HSS8X8X1/2. CLARIFY.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2014 CPIERCE1 OUT TO CUSTOMER Completed
02/06/2014 CPIERCE1 REJECT SHELF Completed