Permit Number: T13CM07532
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM07532
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 3; SHEET S3.0 (PLAN); SHEET S4.0 (ELEVATION): THE COLUMN DESIGNATIONS ON THE PLAN STILL DO NOT MATCH THOSE ON THE ELEVATION. THE LOCATION OF THE ELEVATION IS STILL NOT INDICATED ON THE PLAN.
2. PREVIOUS COMMENT 4; SHEET S3.0 (PLAN); SHEET S5.0: COLUMN DETAIL 3/S5.0 IS STILL NOT LOCATED ON THE PLAN.
3. PREVIOUS COMMENT 5; SHEET S3.0 (PLAN); SHEET S5.0 (DETAILS 2 AND 4): DETAILS 2/S5.0 AND 4/S5.0 ARE STILL NOT LOCATED ON THE PLAN.
4. PREVIOUS COMMENT 6; SHEET S3.0 (PLAN); SHEET S4.0 (ELEVATION): THE REFERENCED COLUMN HEIGHTS ON SHEET S4.0 WERE STILL NOT CLARIFIED AS TO THE REFERENCED TOP OF COLUMNS INDICATED ON SHEET S3.0.
5. PREVIOUS COMMENT 7; SHEET S5.0; DETAIL 1: THE DETAIL IS STILL NOT INDICATED ON 3/S5.0.
6. PREVIOUS COMMENT 8; SHEETS S5.1, S5.2, AND S5.3; COLUMNS: NO ADDITIONAL DETAILS WERE PROVIDED FOR CLARIFICATION OF THE NEW COLUMN CONNECTIONS.
7. GENERAL: FOR THE NEXT SUBMITTAL, THE TWO SETS MUST INCLUDE ALL OF THE SHEETS (ORIGINAL COVER SHEET, ORIGINAL SHEET OC-102, ORIGINAL SHEET OL-100, AND REVISED SHEETS S1.0, S1.1, S2.0, S3.0, S4.0, S5.0, S5.1, S5.2, S5.3, AND S5.4, ALL STAMPED, SIGNED, DATED.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2014 FERNE RODRIGUEZ REJECT SHELF Completed