Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM07484
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/18/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A3; FLOOR PLAN: THE FOUR ENLARGED PLANS ALL INDICATE SHEET A3. REVISE TO A4. 2. SHEET A4; KEYNOTES: NOTES 5 AND 8 WERE NOT LOCATED ON THE PLANS/ELEVATIONS. VERIFY. 3. SHEET A4; FRAMING PLANS 3 AND 4: THE HSS 6X6X1/4 AGAINST THE BUILDING WALL WAS NOT CALLED OUT ON THESE PLANS. VERIFY. 4. SHEET A5; KEYNOTE 2: THE NOTE REFERENCES DETAIL 1/A6. REVISE TO SHEET A5. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/02/2014 | CPIERCE1 | REJECT SHELF | Completed |