Permit Number: T13CM07461
Parcel: 117110730

Address:
160 E ALAMEDA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM07461
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied While there is no requirement to install drinking fountains in an existing building that does not already have drinking fountains, the International Existing Building Code also does not have provisions allowing the deletion of an existing drinking fountain without installing a replacement drinking fountain (see plan 1/P101). The replacement drinking fountain shall comply with all current code requirements for features and accessibility. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountain, service sink, etc.). See also Section 1109.5.1, IBC 2012.]