Permit Number: T13CM07461
Parcel: 117110730

Address:
160 E ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07461
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountain, service sink, etc.). See also Section 1109.5.1, IBC 2012.
2. Indirect waste receptors shall be installed in ventilated locations with ready access. Reference: Sections 202 and 802.3, IPC 2012.
01/02/2014 ROBERT SHERRY WATER REVIEW Approved
01/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Demonstrate energy code compliance for the alterations to the building envelope (e.g. new skylights, new glazing) using calculations based on the current code. Provide sufficient detail on the drawings to confirm the energy compliance of the alterations to the building envelope. The information shall, as a minimum, include the U-factors and the SHGC of the fenestration components. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
12/13/2013 MARTIN BROWN FIRE REVIEW Approved
12/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Completed
12/20/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-000; DRAWING INDEX: THE INDEX DOES NOT INCLUDE SHEET A-008 (SPECIFICATIONS). VERIFY.
2. SHEET A-001; GOVERNING REGULATIONS: REVISE THE ICC/ANSI TO THE 2009 EDITION.
3. SHEET A-102; CONSTRUCTION PLAN: THE ELEVATION REFERENCE IN THE KITCHENETTE (ROOM 09) INDICATES 12/A-700. REVISE.
4. SHEET A-102; KEY NOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY.
5. SHEETS A-102 AND A-103; PLANS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE MISCELLANEOUS NOTES ON THE PLANS.
6. SHEET A-200: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ELEVATION NOTES.
7. SHEET A-201: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ELEVATION NOTES.
8. SHEET A-300: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE BUILDING SECTION 5 NOTES.
9. SHEET A-400: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SECTION NOTES.
10. SHEET A-500: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SECTION NOTES.
11. SHEET A-501: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DETAIL NOTES.
12. SHEET A-600: IF THE INTERIOR PARTITION WALLS DO NOT EXTEND TO THE STRUCTURE ABOVE, PROVIDE BRACING AT THE TOP OF THE WALL TO RESIST HORIZONTAL LOADING PER THE IBC SECTION 1607.14. ON THE DRAWINGS, INCLUDE A DETAIL FOR THE BRACING THAT INDICATES BRACING SIZE AND SPACING, AND SHOW THE CONNECTION OF THE BRACING TO THE PARTITION WALL AND TO THE STRUCTURE ABOVE. IF THE PARTITIONS EXTEND TO THE STRUCTURE ABOVE, INDICATE ON THE DRAWINGS HOW THE WALL IS CONNECTED TO THE STRUCTURE.
13. SHEET A-600: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE FRAME NOTES.
14. SHEET A-700; DETAIL PLAN 1: THE ELEVATION REFERENCE IN THE KITCHENETTE (ROOM 09) INDICATES 12/A-700. REVISE.
15. SHEET A-700; ELEVATION 2: THE SINK HEIGHT SHOULD BE 2'-10" ABOVE THE FINISH FLOOR. VERIFY.
16. SHEET A-700: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ELEVATION AND PLAN NOTES.
17. STRUCTURAL CALCULATIONS: NO STRUCTURAL CALCULATIONS WERE SUBMITTED FOR THE NEW LINTELS, COLUMNS, OR FOOTINGS. PROVIDE.
18. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2014 CPIERCE1 REJECT SHELF Completed