Permit Number: T13CM06987
Parcel: 141148150

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06987
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2013 STEVE SHIELDS ZONING REVIEW Approved
11/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the proposed HVAC controls meet the requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.
2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
3. Show how adequate make-up air is to be provided to the suite so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2012.
11/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm06987
9040 E Valencia

1. See Mechanical comments, the switching for ex-fans in restrooms to be per 2012 IMC 403.2.1(4).
2. Restrooms receptacles to be GFIC protected.
3. Show locations of lighting contactors.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
11/18/2013
Ray.Majuta@tucsonaz.gov
520-837-4988
11/18/2013 ROBERT SHERRY WATER REVIEW Approved
11/18/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/18/2013 CPIERCE1 WWM REVIEW Completed
11/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference: Section 107.2.1, IBC 2012.
2. Coordinate the fixture description for the water closet: wall-mounted or floor-mounted. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
3. Provide tempered water for the lavatories and public hand-washing sinks using approved devices conforming to ASSE 1070. The specified mixing valve is not recognized on the Leonard website. Reference: Sections 416.5 and 607.1.2, IPC 2012.
4. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2012.
5. The design of the water heater piping, with a valve located between the water heater and the expansion tank, makes it impossible for the expansion tank to accommodate the thermal expansion of the water in the water heater, as intended by Section 607.3, IPC 2012.
6. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
7. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for mercantile occupancy (i.e. a bottled water dispenser is not accepted as a substitute for the required single water fountain).
11/18/2013 LOREN MAKUS ENGINEERING REVIEW Approved
11/18/2013 CPIERCE1 FIRE REVIEW Denied Need to know the existing fire sprinkler design to be able to give credit for sprinklers to increase the storage quantities.
Please provide the NFPA 704 label descriptions and where they will be provided.
Please indicate if you are providing exhaust ventilation for the entire building or just in the storage area.
Please indicate how compliance will be met for sections 5003.11.3.1 through 5003.11.3.10 of the 2012 IFC
11/18/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved