Permit Number: T13CM06261
Parcel: 13507439B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM06261
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2013 STEVE SHIELDS ZONING REVIEW Approved
10/14/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the installation the exhaust duct for the kitchen exhaust system with regard to slope and fire wrap (detail K11 and Keynote 3 on M101).
10/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2013 ROBERT SHERRY WATER REVIEW Approved
10/14/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/14/2013 LOREN MAKUS ENGINEERING REVIEW Approved
10/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that all of the vents (indoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
2. Revise keynote 6 on sheet P101 to indicate that the 3-compartment sink is to be indirectly connected to the grease waste system.
3. Revise the waste and vent riser diagram to show the all compartments of the 3-compartment sink indirectly connected to the grease wate system.
4. Revise the Plumbing Equipment List and Connection Schedule to indicate that the all compartments of the 3-compartment sink are to be indirectly connected to the grease wate system.
10/14/2013 KEN BROUILLETTE FIRE REVIEW Approved
10/14/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/31/2013 SPOWELL1 WWM REVIEW Needs Review