Permit Number: T13CM05871
Parcel: 10306092G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM05871
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond STANDBY OR EMERGENCY POWER IS REQUIRED FOR THE VENTILATION SYSTEM PER IFC 5004.7
10/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/09/2013 ROBERT SHERRY WATER REVIEW Approved
10/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approv-Cond The water service valve for the building shall be accessible and located on the exterior of the building per section 606.3, IPC 2012.