Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Address NEW:
2550 W SWEETWATER DR
Apply Date:
09/24/2013
Applicant:
JOY TERRY
Description:
NEW AMMONIA BUILDING FOR TREATMENT PLANT
Contractors:
  • C H 2 M HILL CONSTRUCTORS INC ,

Permit Reviews

Permit Number - T13CM05871
Permit Status: C of o
Permit Description: NEW AMMONIA BUILDING FOR TREATMENT PLANT
Start Date Submittal Complete Date Status  
09/24/2013 PLANS OK TO SUBMIT - COMM 09/24/2013 COMPLETED Review Details
09/24/2013 COMMERCIAL - NEW 10/07/2013 COMPLETED Review Details
10/09/2013 RESUBMITTAL 10/09/2013 COMPLETED Review Details
12/06/2013 REVISION - - 1ST 12/06/2013 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T13CM05871
Permit Status: C of o
Permit Description: NEW AMMONIA BUILDING FOR TREATMENT PLANT
Total Outstanding Activity Conditions - 1
Date Name
09/24/2013 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T13CM05871
Permit Description: NEW AMMONIA BUILDING FOR TREATMENT PLANT
Total Completed Inspections - 32
Date Description Inspector Results Comments
11/04/2013 PLUMBING - YARD WTR LINE/TEST RMYERS Approved 1. 30" DIP reclaimed tied into existing OK. OK to cover.
11/08/2013 ELECTRIC - UFER DQUINN Approved
11/08/2013 EXCAVATION/LAYOUT REBAR & ZON DQUINN Approved MAIN AMONIA BUILDING MATS AND UFER OK TO POUR
11/13/2013 STEM WALL/RETAINING WALL MPUGH Approved STEM WALL OK TO POUR
11/13/2013 STEM WALL/RETAINING WALL MPUGH Approved IVRS - Inspection :*
11/18/2013 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved
11/18/2013 FIRE SPKLR - UG, PIPING, HYDRO CSCHULTZ Approved 200 PSI for 2 hours
11/26/2013 BUILDING - PROGRESS RMYERS Approved 1. Bonding grid OK. Electric conduit around building and extended ten plus feet South of building OK to cover.
12/10/2013 PLUMBING - INTERMEDIATE RMYERS Approved 1. Ten feet of 36" DIP installed just outside Chlorine Basin.
12/12/2013 ELECTRIC - UNDERGROUND MPUGH Approved NEW DUCT BANK OK TO COVER
12/12/2013 ELECTRIC - UNDERGROUND MPUGH Approved IVRS - Inspection :*
12/19/2013 REINFORCED MASONRY PRE-GROUT RMYERS Approved
01/22/2014 ROOF NAILING RMYERS Approved
01/28/2014 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 2 HOURS AND PLACEMENT - APPROVED- CHANGES WERE MADE TO SPRINKLER HEADS PLANS SHOW 155 DEG INSTALLED ARE 200 DEG. HEADS NO COOLER OR A/C FOR ROOM.
02/20/2014 ELECTRIC - ABOVE CEILING RMYERS Approved
02/20/2014 MECHANICAL - INTERMEDIATE RMYERS Approved
02/20/2014 EXT METAL CLIPS/EXT SHEATHING RMYERS Approved
02/20/2014 BUILDING PRE-SLAB RMYERS Approved
03/07/2014 RIGHT OF WAY - FINAL TW Approved
03/10/2014 ELECTRIC - INTERMEDIATE RMYERS Approved
03/10/2014 ELECTRIC - SERVICE UPGRADE RMYERS Approved
03/10/2014 NPPO - FINAL MRUSSO Approved
03/10/2014 SIGN - FINAL MRUSSO Approved
03/10/2014 LANDSCAPE - FINAL MRUSSO Approved
03/10/2014 ENGINEERING - FINAL MRUSSO Approved
03/17/2014 FIRE SPKLR - FINAL CSCHULTZ Approved 2" drain test 100-90-100
03/17/2014 FIRE - ALARM FINAL CSCHULTZ Approved
03/21/2014 ELECTRIC - FINAL RMYERS Approved
03/21/2014 PLUMBING - FINAL RMYERS Approved
03/21/2014 MECHANICAL - FINAL RMYERS Approved
03/24/2014 FIRE - FINAL CSCHULTZ Approved
04/04/2014 BUILDING - FINAL RMYERS Approved