09/25/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T13CM05405
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Include sheets S1.X and S2.X.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

STRUCTURAL PLANS:

1. Add sheets S1.X and S2.X as listed on Sheet Index and Keynotes/A5.0, R301.1. Show all construction on the plans.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.

PLUMBING PLANS:

1. Show an individual water heater for each dwelling unit, P2801.1.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show the total developed length (TDL) from meter to the most remote appliance on the system, and correct the size of the supply pipe for the total connected and future demand. The 1-1/2" pipe is undersized for a (779 CFH) system with TDL over 60 foot in length.

MECHANICAL PLANS:

1. Show a heating appliance in all habitable rooms, R303.8. Include the Guest House.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Show receptacle outlets at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2.
3. Show Bathroom receptacles on a 20 AMP circuit, E3703.4. Include the Guest House circuit #9.
4. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
5. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.13.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Show the maximum "U" factors of replaced windows, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2013 CPIERCE1 REJECT SHELF Completed