Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM05040
Parcel: 136129500

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05040
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow (see detail E13/P100). Reference: Sections 708.3.5 and 708.5, IPC 2012.
08/30/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify the termination point of the overflow roof drains. Condensate drains may not terminate over a roof drain unless the roof drain itself terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Revise plans as required to provide a separation of at least ten feet between air intake openings and exhaust openings. Reference: 401.4 (2), IMC 2012.