Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM04749
Parcel: 140290480

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM04749
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide a written description of the changes on each sheet of the documents.
SHEET A1.1
2. By closing off the partition, how does onme access the break room?
a. Cordinate all note references so that they have meaning and are pointing to the correct changed element.
3. Provide a room name and number to the new space. created just behind roll up door 135D.
a. Is there to be an access from this new room to the warehouse 135?
b. Cordinate all note references so that they have meaning and are pointing to the correct changed element.
END OF REVIEW
10/23/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit, HP-13. Reference: Section 302.1, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2013 CPIERCE1 REJECT SHELF Completed