| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide a written description of the changes on each sheet of the documents. SHEET A1.1 2. By closing off the partition, how does onme access the break room? a. Cordinate all note references so that they have meaning and are pointing to the correct changed element. 3. Provide a room name and number to the new space. created just behind roll up door 135D. a. Is there to be an access from this new room to the warehouse 135? b. Cordinate all note references so that they have meaning and are pointing to the correct changed element. END OF REVIEW |
| 10/23/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit, HP-13. Reference: Section 302.1, IMC 2012. |