Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T13CM04749
Parcel: 140290480

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM04749
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/03/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The 8" diameter outside air duct enters the return air duct prior to the duct smoke detector. [Initial comment: Smoke detectors shall be located upstream of any outside air connections (AC-1). Reference: Section 606.2.1, IMC 2012.]
09/03/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; no change has been made to the detail other than to enclose it with a cloud. Provide information to show that the installation of the thermal expansion tank for the water heater (detail 15/M6.1) complies with the manufacturer's listing requirements (i.e. on the cold water supply line, between the water heater and the backflow preventer or other one-way device). Reference: Sections 303.2 and 607.3.2, IPC 2012.
2. Comment not resolved; no change has been made to the detail other than to enclose it with a cloud. Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012.
09/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
09/12/2013 CPIERCE1 REJECT SHELF Completed