Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM04749
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/03/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The 8" diameter outside air duct enters the return air duct prior to the duct smoke detector. [Initial comment: Smoke detectors shall be located upstream of any outside air connections (AC-1). Reference: Section 606.2.1, IMC 2012.] |
09/03/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; no change has been made to the detail other than to enclose it with a cloud. Provide information to show that the installation of the thermal expansion tank for the water heater (detail 15/M6.1) complies with the manufacturer's listing requirements (i.e. on the cold water supply line, between the water heater and the backflow preventer or other one-way device). Reference: Sections 303.2 and 607.3.2, IPC 2012. 2. Comment not resolved; no change has been made to the detail other than to enclose it with a cloud. Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012. |
09/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/12/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
09/12/2013 | CPIERCE1 | REJECT SHELF | Completed |