Permit Number: T13CM04494
Parcel: 11310001A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM04494
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2013 KEN BROUILLETTE FIRE REVIEW Approved
09/10/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The total gas load shown on detail 2/M8.3 for the branch serving the kitchen and the rooftop units on the west side of the building has been changed from 2133 CFH to 2820 CFH. As none of the individual gas loads have been altered, what is the basis for the new total connected gas load? [Initial comment: Verify the developed pipe lengths to each of the gas loads; the developed length from the meter to AC-7, for example, is approximately 195-feet, not the 140-feet shown on detail 13/M6.3. Reference: Section 402.4, IFGC 2012.]
09/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The reply to the comments indicated that the rooftop units were specified to have a barometric relief for the excess air. The specifications on sheet M9.1 do not call for a barometric relief damper. [Initial comment: Clarify how excess outside air relief from the building is to be accomplished. Reference: Section C403.3.1.1.4, IECC 2012.]
09/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/23/2013 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: T13CM04494
1545 E Copper Street
Salpointe Student Center Buildings

TRANSMITTAL DATE: September 23, 2013

DUE DATE: October 3, 2013

COMMENTS: Zoning will review and stamp the building plan set over the counter once the building plans have approved by the Mechanical/Plumbing plans reviewer and the development package has been approved by review and signed off by the CDRC Manager

01. Zoning has reviewed the plans but cannot approve them at this time. While the building plans appear to be consistent with the development package site plan zoning cannot approve the building plans until the development package is approved.

02. If any changes are made to the development package site plan that affects the design of the building whether height, GFA etc changes to the building or site plan must be made as required for consistency between the plans.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
09/23/2013 JASON GREEN ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2013 SHANAE POWELL OUT TO CUSTOMER Completed
10/01/2013 CPIERCE1 REJECT SHELF Completed