Review Details: RESUBMITTAL

Permit Number - T13CM03807
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Reqs Change T13CM03807
1540 E Glenn ST
70,000W PV System At Carmalite Priory

1. With the new addition of the 1200 A CT enclosure,
Sheet 3110-04 shows a new grounding point at this new enclosure. What size conductor to be installed and what will it be connected to? What will happen at the existing SES grounding tie?
2. Sheet 3110.01 shows an overhead view of equipment,
one and three line diagrams show flow of installation , would you provide a detail of how on site it will look once installed, just the AC/PV disconnect, new 1200 amp CT and the existing SES.


Ray T Majuta
Elect Plan Review
PDSD, Tucson
8/19/2013