| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/19/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T13CM03807 1540 E Glenn ST 70,000W PV System At Carmalite Priory 1. With the new addition of the 1200 A CT enclosure, Sheet 3110-04 shows a new grounding point at this new enclosure. What size conductor to be installed and what will it be connected to? What will happen at the existing SES grounding tie? 2. Sheet 3110.01 shows an overhead view of equipment, one and three line diagrams show flow of installation , would you provide a detail of how on site it will look once installed, just the AC/PV disconnect, new 1200 amp CT and the existing SES. Ray T Majuta Elect Plan Review PDSD, Tucson 8/19/2013 Ray.Majuta@tucsonaz.gov |