Permit Number: T13CM03807
Parcel: 11310001A

Address:
1540 E GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM03807
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM03807
1540 E Glenn
Salpointe School , 70 KV PV System

1. Per City of Tucson Submittal Requirements show locations on plans for following items, SES, AC (PV) disconnect, DG meter, inverter, recombiner, combiner boxes and combiner disconnects.
2. Provide fault current values at SES and for new equipment per NEC 2011,110.9, 690.14.A, and 16, also per 705.14 and 16.
3. Is the existing SES approved for a line side termination in that are there pre drilled holes in the bussing or are existing terminals provided ? Is room available in line side cubicle for conductors ? This installation may require a third party certification on changes to the existing SES (NEC 110.3)
4. A three line diagram is required as well as the one line submitted.
5. Describe intention of the junction box next to SES. How will it be attached to the SES and connection be made weather-proof ? If box has a removeable cover can it be locked ?
6. Are the Polaris connectors to be used in the junction box listed for the AIC at the SES ? Provide a spec sheet if listed.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
7/9/2013
Ray.Majuta@tucsonaz.gov
520/837/4988
07/10/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide details and sections of the existing shade structure and PV panel connections.
2. Please provide Inverter structural details on the drawings, foundation and cabinet connections.
3. Please provide certification of the required special inspectors as outlined on sheet S1.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
08/14/2013 CPIERCE1 REJECT SHELF Completed