Permit Number: T13CM03780
Parcel: 11615077C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM03780
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2: SHEET A1; DRINKING FOUNTAIN ELEVATION D: PER THE INTERNATIONAL PLUMBING CODE SECTION 410.2, A HIGH/LOW DRINKING FOUNTAIN IS REQUIRED. AS AN ALTERNATIVE, THE CITY OF TUCSON ALLOWS A SINGLE POINT-OF-USE WATER DISPENSER IN LIEU OF THE HIGH/LOW FOUNTAIN. REVISE THE ELEVATION. THIS COULD BE PART OF THE 20% ACCESSIBILITY UPGRADE AS DESCRIBED IN NOTE 6 OF THESE COMMENTS. THE DRINKING FOUNTAIN DETAILED ON SHEET A1 NEEDS TO INDICATE THE HIGH/LOW FOUNTAIN, SINCE THE OASIS DRINKING FOUNTAIN MODEL IS HIGH/LOW.
07/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
07/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved