Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
06/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide 0.7 CFM / Square foot exhaust for the kitchen (each appliance that does not require a Type II hood is considered to occupy at least 100 square feet). Reference: Sections 403.3 and 507.2.2, IMC 2012.
06/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify the size of the hydromechanical grease interceptor - at 30" in total height, it won't fit under the sink.
2. External flow control devices are not required for the specified grease interceptor and thus constitute obstructions in the waste piping.
3. Provide a thermostatic mixing valve for each lavatory that conplies with ASSE 1070.
06/05/2013 ROBERT SHERRY WATER REVIEW Approved
06/05/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/05/2013 JASON GREEN ENGINEERING REVIEW Approved
06/05/2013 KEN BROUILLETTE FIRE REVIEW Approved
06/05/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/11/2013 CPIERCE1 WWM REVIEW Needs Review
06/11/2013 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review