Permit Number: T13CM02748
Parcel: 115044900

Address:
1031 N PARK AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM02748
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Sheet P103 shows a 4" roof drain leader and a 4"overflow roof drain leader, each serving 3200 square feet of roof, running horizontally with a slope of 1/8" per foot. Per Table 1106.3, IPC 2012, the maximum capacity of a 4" pipe with a slope of 1/8" per foot is 2506 square feet.
10/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify that the equivalent lengths of the dryer exhaust ducts located in room types X12, X12.1, and X12.2 are less than 35 feet. If the equivalent duct lengths exceed 35 feet, provide the dryer manufacturer's installation instructions for review. Reference: Sections 504.6.4.1, 504.6.4.2, and 504.6.5, IMC 2012.
10/28/2013 MARTIN BROWN FIRE REVIEW Approv-Cond THE BUILDING WILL BE REQUIRED WITH ALL HIGH-RISE REQUIREMENTS FROM THE IFC AND IBC 2012 EDITIONS. ALL APPROVALS ARE SUBJECT TO FIRE INSPECTOR APPROVAL. CONTRACTOR SHALL COMPLY WITH IFC CHAPTER 33 DURING CONSTRUCTION

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2013 CPIERCE1 OUT TO CUSTOMER Completed
11/18/2013 CPIERCE1 REJECT SHELF Completed