Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/06/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a complete plumbing plan, including water isometrics as well as waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
2. Clarify how the neutralization trap and the island venting detail will function. Reference: Sections 303.2 and 916.3, IPC 2012.
3. Provide the listing for the two-way cleanout fitting called out in detail 11/P2.1. Reference: Section 708.3.5, IPC 2012.
4. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012
5. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Include the area of vertical surfaces that divert rainwater to the roof sections and contributory horizontal areas in the calculations. Note the effect of crickets that divide the roof into discrete areas when evaluating which roof sections will be affected by contributory water flow. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.
6. Clarify the size and type (i.e. CW only or CW plus HW) of the water service to the emergency shower/eyewash station: detail 4/P2.1 shows a 1-1/4" CW supply to the emergency shower/eyewash station, the plumbing schedule calls to a 1-1/2" CW and a 1-1/2" HW to the same station but the plumbing plans show a 1" CW supply serving a sink and the emergency shower/eyewash station.
7. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012.
05/06/2013 ROBERT SHERRY WATER REVIEW Approved
05/08/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1.0; BUILDING OCCUPANCY: THE TOTAL NUMBER OF OCCUPANTS LISTED IN THIS SECTION (1710) DOES NOT CORRESPOND TO THE NUMBER LISTED IN THE PLUMBING FIXTURE CALCULATION (948). THE NOTE AT THE OCCUPANCY LOAD TABLE ON SHEET A0.0 INDICATES APPLICATION TO THE BUILDING OFFICIAL FOR AN OCCUPANCY REDUCTION. HAS THIS APPEAL BEEN SUBMITTED? VERIFY AND PROVIDE.
2. SHEET T1.0; BUILDING OCCUPANCY: THE EXITS ARE DETERMINED PER TABLE 1019.1. CHANGE THIS REFERENCE TO THE 2012 IBC, AND RUN A NEW CALCULATION FOR THE REQUIRED NUMBER OF EXITS AT EACH FLOOR.
3. SHEET T1.0 (BUILDING OCCUPANCY); SHEET A0.0 (REQUIRED NUMBER OF EXITS): SHEET T1.0 INDICATES 7 EXITS PROVIDED, WHILE SHEET A0.0 INDICATES 6. CLARIFY.
4. SHEET A0.0; OCCUPANT LOAD CALCULATION: THE NOTE FOR THE BUILDING OFFICIAL APPROVAL OF A REDUCTION IN THE TOTAL OCCUPANT LOAD REFERENCES THE IBC SECTION 1004.1.1. REVISE THAT REFERENCE TO THE 2012 IBC.
5. SHEET A0.0; EXIT REQUIREMENTS: REVISE THE REFERENCE TO THE DEAD END CORRIDOR LENGTH (SECTION 1017.3) TO THE 2012 IBC.
6. SHEET A0.0; EXIT REQUIREMENTS: REVISE THE REFERENCE TO THE EGRESS WIDTH (TABLE 1005.3.2) TO THE 2012 IBC, AND REVISE THE CALCULATION AS REQUIRED.
7. SHEETS A2.0 AND A2.1; FLOOR PLAN KEYNOTES: PROVIDE A NOTE INDICATING KEYNOTES NOT LOCATED ON ONE SHEET MAY BE ON THE OTHER SHEET.
8. SHEETS A2.0 AND A2.1; FLOOR PLAN KEYNOTES: NOTES 2, 9, 10, AND 11 WERE NOT LOCATED ON EITHER PLAN. VERIFY.
9. SHEET A2.0; FLOOR PLAN: IN THE SOUTHWEST CORNER ROOM, MOVE THE DIMENSION LINE TO MAKE THE ROOM IDENTIFICATION LEGIBLE.
10. SHEETS A2.0 AND A2.1; FLOOR PLAN KEYNOTES: NOTE 7 WAS NOT LOCATED ON EITHER PLAN. VERIFY.
11. SHEET A2.1; FLOOR PLAN: A WALL TAG NEAR GRIDS K AND 6 IS INCOMPLETE. PROVIDE.
12. SHEET A2.1; WALL TYPES: CLEAR UP THE VERBIAGE AT THE TITLE.
13. SHEET A2.2; PLAN: REVISE THE NORTH ARROW DIRECTION.
14. SHEET A2.2; PLAN: MOVE THE DIMENSION LINES ON THE NORTH SIDE OF THE BUILDING.
15. SHEET A2.2; PLAN: MOVE THE GRID LINE DESIGNATIONS AWAY FROM THE DIMENSION LINE ON THE SOUTH WALL.
16. SHEETS A2.5, A2.6, AND A2.7; KEYNOTES: VERIFY KEYNOTES LISTED ARE LOCATED ON THE PLANS AND PERTINENT TO THAT PLAN.
17. SHEET A5.0; ACCESSIBILITY: VERIFY THE WATER CLOSET HEIGHT, PAPER DISPENSER LOCATION, URINAL HEIGHTS, AND GRAB BAR HEIGHTS FOR CHILDREN PER THE 2009 ICC/ANSI, AND REVISE THOSE DIMENSIONS ON THE DRAWINGS AS REQUIRED.
18. SHEETS A5.2 AND A5.3; MILLWORK: VERIFY THE WORK SURFACES INDICATED MEET THE REQUIREMENTS FOR CHILDREN PER THE ICC/ANSI CHAPTER 9 (WHERE APPLICABLE).
19. SHEET S2.0; FOUNDATION PLAN: IS DETAIL 110 CUT ON THE FOUNDATION PLAN, OR SHOULD IT BE CUT ON DETAIL 109? CLARIFY.
20. SHEET S2.0; DETAILS 102 AND 103: DETAIL 102 IS TITLED AS AN EXTERIOR STUD WALL FOOTING, BUT IS CUT AT INTERIOR LOCATIONS ON THE PLAN. DETAIL 103 IS TITLED INTERIOR STUD WALL FOOTING, BUT IS CUT AT EXTERIOR LOCATIONS ON THE PLAN. CLARIFY.
21. SHEETS S3.0 AND S3.1; FRAMING PLAN NOTES: PROVIDE A NOTE INDICATING KEYNOTES NOT LOCATED ON ONE SHEET MAY BE ON THE OTHER SHEET.
22. SHEETS S3.0 AND S3.1; FRAMING PLAN NOTE 7: THE ROOF HATCH WAS NOT LOCATED ON THE PLANS. VERIFY.
23. SHEETS S3.0 AND S3.1; FRAMING PLAN NOTES 9,13, AND 17: THESE NOTES WERE NOT LOCATED ON THE PLANS. VERIFY.
24. SHEET S3.1 (FRAMING PLAN); SHEET S5.0 (DETAIL 215B): WHERE IS DETAIL 215B CUT ON THE PLAN? VERIFY.
25. SHEET S4.0: INDICATE ON DETAIL 102 THAT THE BOTTOM OF THE FOOTING SHOULD BE LOCATED TYPICALLY 1'-6" BELOW THE LOWEST ADJACENT GRADE (PER FOUNDATION GENERAL NOTE 1 ON SHEET S1.0).
26. SHEET S4.0: INDICATE ON DETAIL 103 THAT THE 1'-6" DIMENSION IS THE MINIMUM DISTANCE FROM THE SLAB TO THE BOTTOM OF THE FOOTING.
27. SHEETS S4.0 AND S4.1; DETAILS 105, 106, 114, AND 122: PROVIDE A MINIMUM DISTANCE FROM THE FINISH FLOOR (OR GRADE) TO THE TOP OR BOTTOM OF THE FOOTING (DEPENDING ON THE COVER DEPTH YOU REQUIRE FOR THE STEEL COLUMN AND BASE PLATE).
28. SHEET S4.0; DETAIL 106: PROVIDE A DETAIL TITLE.
29. SHEET S5.1; DETAIL 243: REVISE THE DETAIL TITLE.
30. STRUCTURAL CALCULATIONS; SHEET 6; SHEET 293: BEAMS DB13 AND DB15 (DESIGNED ON SHEET 8 AS W12X26) SHOULD BE REFERENCED TO CALCULATIONS ON SHEETS 291 THROUGH 309. VERIFY.
31. STRUCTURAL CALCULATIONS; SHEET 130: WHERE ARE THE WINDOW POP-OUT COLUMNS AND BEAMS INDICATED ON THE PLAN? CLARIFY (INDICATED AS DETAILS 109 AND 110?).
32. GENERAL; SHEETS A2.0 AND A2.1: VERIFY THE FLOOR PLAN KEYNOTES FOR LEVEL1 AND LEVEL 2 ARE INDICATED ON THE PLANS (FOR EXAMPLE, KEY NOTE 16 SHOULD BE ON THE ROOF PLAN ONLY).
33. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. SUBSEQUENT REVIEWS WILL NOT BE PERFORMED UNTIL RESPONSES ARE RECEIVED.
05/08/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/08/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Show that the proposed HVAC system and equipment meets the requirements of Sections C403.2 and C403.3, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code. 2012.
3. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
4. Show the size, routing, and termination of the condensate drains and, if used, the secondary condensate drains. Reference: Sections 307.2.1, IMC 2012 as amended by the City of Tucson.
5. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference: Section 307.2.3 IMC 2012.
6. Provide calculations demonstrating adequate ventilation using the current code. Systems serving multiple zones shall be individually calculated. Reference: Section 403.2, IMC 2012.
7. Revise the sequence of operation for restroom exhaust fans EF-3 through EF-9 so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012.
8. Provide information to show that the elevator machine room does not require an independent venting or air conditioning system to prevent overheating of the elevator equipment. Reference: Section 3006.4, IBC 2012.
05/09/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond CHARTER SCHOOLS ARE UNDER THE STATE OF ARIZONA FIRE MARSHAL'S REVIEW IN THE CITY OF TUCSON. PER THE STATE, NO CONSTRUCTION CAN OCCUR UNTIL THE PLANS ARE REVIEWED AND APPROVED BY THE STATE FIRE MARSHAL'S OFFICE.
05/10/2013 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2013 CPIERCE1 REJECT SHELF Completed