Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM01691
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/29/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/29/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the island venting shown in detail A/P1.1 to show the low point of the vent connecting to the drain downstream of the fixture drain. Reference: Section 916.2, IPC 2012. [Original comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |
| 04/29/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/09/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 05/14/2013 | CPIERCE1 | REJECT SHELF | Completed |