Permit Number: T13CM01493
Parcel: 14117007D

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T13CM01493
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2013 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied The decision letter for the special exception must be submittted with the plan set as a condition of approval.
03/18/2013 MICHAEL ST. PAUL ZONING REVIEW Denied The decision letter for the special exception must be submittted with the plan set as a condition of approval.
03/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T-1; CODE COMPLIANCE: REMOVE THE IRC FROM THIS LIST.
2. SHEET T-1; CODE COMPLIANCE: THE IBC, IPC, AND IMC CURRENTLY USED ARE THE 2012 EDITION. REVISE.
3. SHEET T-1; CODE COMPLIANCE: THE ELECTRICAL CODE CURRENTLY USED IS THE 2011 EDITION OF THE NEC. REVISE.
4. GENERAL: ENSURE THE PLANS MEET THE REQUIREMENTS OF THE NEW CODES LISTED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/21/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
04/15/2013 CPIERCE1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed