Permit Number: T13CM00994
Parcel: 14043013B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00994
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2013 TERRY STEVENS ZONING REVIEW Passed
02/26/2013 MARTIN BROWN FIRE REVIEW Approved
03/01/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S120; CHAMBER FLOOR PLAN: THE ELEVATION INDICATOR ON THE SOUTH WALL (C/S120) SHOULD BE MOVED SO IT IS LEGIBLE.
2. SHEET S510; DETAIL 5: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
3. SHEET S511: DARKEN DETAILS 3, 4, 5, AND 6 SO THEY ARE LEGIBLE.
4. SHEET S511; DETAILS 3, 4, 5, AND 6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
5. GENERAL: THE CITY OF TUCSON REQUIRES TWO SETS OF STRUCTURAL CALCULATIONS TO BE SUBMITTED WITH THE REVIEW SET. PROVIDE.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/12/2013 ROBERT SHERRY WATER REVIEW Passed
03/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed