Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2013 MARTIN BROWN FIRE REVIEW Approved
02/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM00411
1160 N Winstell BL
New 125KVA Generator Installation

1. Sheet E2.0, indicate the conductor size of the grounding and bonding conductor used to connect the new generator and the existing MSB grounding system. Indicate the size of the existing system conductor size.
2. Sheet E2.0, how is determined that the parallel feeders from the new generator to new Panel GA can be allowed to have a reduced neutral of 1/0 cu when using 4/0 cu
phases ?

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
2/20/2013