Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM00411
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM00411 1160 N Winstell BL New 125KVA Generator Installation 1. Sheet E2.0, indicate the conductor size of the grounding and bonding conductor used to connect the new generator and the existing MSB grounding system. Indicate the size of the existing system conductor size. 2. Sheet E2.0, how is determined that the parallel feeders from the new generator to new Panel GA can be allowed to have a reduced neutral of 1/0 cu when using 4/0 cu phases ? Ray T Majuta Elect Plan Review PDSD, City of Tucson 2/20/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/20/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |