Permit Number: T13CM00407
Parcel: 125120810

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00407
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET PV0.0: A NOTE INDICATES THE AUTOMATIC SPRINKLER SYSTEM WILL BE A DEFERRED SUBMITTAL. ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV.
2. SHEET 2 OF 4; DETAIL 3: A DETAIL CUT INDICATES 4/2. REVISE THE DETAIL REFERENCE.
3. SHEET 4 OF 4; GENERAL STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 REFERENCES THE 2006 IBC. REVISE.
4. SHEET 4 OF 4 (GENERAL STRUCTURAL NOTES); STRUCTURAL CALCULATIONS (PAGE 1): THE STRUCTURAL STEEL GENERAL NOTES INDICATE 'ALL BOLTS IN STRUCTURAL CONNECTIONS ARE TO CONFORM TO ASTM A307, UNLESS NOTED ON THE DRAWINGS'. NO NOTE WAS FOUND ON THE DRAWINGS, BUT THE STRUCTURAL CALCULATIONS INDICATE ASTM A325 STEEL FRAME BOLTS. CLARIFY.
5. STRUCTURAL CALCULATIONS; PAGE 1: UNDER 'DESIGN CRITERIA', THE 2006 IBC IS LISTED. REVISE.
6. STRUCTURAL CALCULATIONS: A NEW SECTION 1609.5.1.1 IN THE CITY OF TUCSON AMENDMENTS TO THE 2012 IBC REQUIRES: "IN ADDITION TO REQUIREMENTS OF ASCE 7, MINIMUM UPLIFT RESISTANCE SHALL BE DETERMINED BY EITHER METHOD 1 OR 2" (LISTED IN THE AMENDMENT). SHOW THE ANALYSIS (STARTING ON PAGE 4 OF THE CALCULATIONS) MEETS THAT REQUIREMENT.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved