Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/05/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT #304 at 1310
South Alvernon Way (T13BU00215).

Sheet 1 of 1

1. Add Subsection 2(f) to Billboard Note #9 to reflect Z-clip replacement.

Sheet 2 of 2

1. Resolve the inconsistency between Z-clip fasteners shown (it would
appear that the metal stingers would require the generally shown tek screws,
yet the scope of work specifies #12 x 1 ¼” (wood) screws).

2. Add Subsection 2(f) to list of Exhibit 9 authorizations to reflect
Z-clip replacement.

3. Clarify if light fixtures and supports are to remain in place during
work (with no movement); if to be rotated or otherwise moved or removed and
reinstalled, provide for a special inspection to assure finished work
complies with the Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed