Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T13BU00215
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/05/2013 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized repair submittal for COT #304 at 1310 South Alvernon Way (T13BU00215). Sheet 1 of 1 1. Add Subsection 2(f) to Billboard Note #9 to reflect Z-clip replacement. Sheet 2 of 2 1. Resolve the inconsistency between Z-clip fasteners shown (it would appear that the metal stingers would require the generally shown tek screws, yet the scope of work specifies #12 x 1 ¼” (wood) screws). 2. Add Subsection 2(f) to list of Exhibit 9 authorizations to reflect Z-clip replacement. 3. Clarify if light fixtures and supports are to remain in place during work (with no movement); if to be rotated or otherwise moved or removed and reinstalled, provide for a special inspection to assure finished work complies with the Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/23/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |