Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM08238
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2013 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1.Plans do not show how the manual fire alarm system requirement in 907.3.1.7 exception 1 of the 2006 IFC will be met. Indicate on plans that exception 1 will be used and specify the walls to be used to meet this requirement if this project wishes not to have a manual fire alarm system. 2. Please indicate how this project will comply with Smoke Alarms per 907.3.2 of the 2006 IFC. 3. Fire Extinguishers will also be required for this project. Please indicate the type and location of installation. |
| 01/14/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET T-1 1. Provide summary of modified units. 2. List code analysis summary for type "A" and type "B" units. 3. At the General Notes and Summary of Governing Regulations, change listed 2003 IBC to 2006 IBC. SHEET M-4 4. Please provide structural calculations for fan coil units FCA4, FCB3, FCB4 AND FCC8. END OF REVIEW |
| 01/22/2013 | SPOWELL1 | WWM | REVIEW | Needs Review | |
| 01/22/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/22/2013 | LHANLY1 | WATER | REVIEW | Approved | |
| 01/22/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/22/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved |