Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM08062
Parcel: 10825287A

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T12CM08062
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2013 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT: YOUR RESPONSE TO THE COMMENT CONCERNING THE WEIGHT OF THE WATER HEATER INDICATES 'THE PLATFORM WILL HOLD THE 200# WATER HEATER', WHILE THE DETAIL INDICATES A WATER HEATER WEIGHT OF 230#. COORDINATE.
2. DETAIL 7/A3: A NOTE BELOW THE ROOF TRUSSES INDICATES 'BOTTOM CHORD OF EXISTING WOOD CHORD STEEL WEB ROOF JOISTS', BUT POINTS TO THE NEW DOUBLE 2X THAT HAS BEEN ADDED. REVISE THE NOTE AND ADD VERBIAGE ON THE CONNECTION OF THAT DOUBLE 2X TO THE BOTTOM CHORD OF THE TRUSSES.
3. DETAIL 7/A3: CALL OUT THE DOUBLE 2X SIZE.
4. DETAIL 7/A3: THE NEW 4X6 CALLS OUT FOR A CONNECTION TO THE 'BOTTOM CHORD OF JOISTS'. IT IS ACTUALLY CONNECTING TO THE NEW DOUBLE 2X. VERIFY.
5. DETAIL 7/A3: A NOTE IN THE 4X6 INDICATES A 200# CAPACITY. REVISE THAT ALLOWABLE LOAD.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.