Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T12CM08062
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2013 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: YOUR RESPONSE TO THE COMMENT CONCERNING THE WEIGHT OF THE WATER HEATER INDICATES 'THE PLATFORM WILL HOLD THE 200# WATER HEATER', WHILE THE DETAIL INDICATES A WATER HEATER WEIGHT OF 230#. COORDINATE. 2. DETAIL 7/A3: A NOTE BELOW THE ROOF TRUSSES INDICATES 'BOTTOM CHORD OF EXISTING WOOD CHORD STEEL WEB ROOF JOISTS', BUT POINTS TO THE NEW DOUBLE 2X THAT HAS BEEN ADDED. REVISE THE NOTE AND ADD VERBIAGE ON THE CONNECTION OF THAT DOUBLE 2X TO THE BOTTOM CHORD OF THE TRUSSES. 3. DETAIL 7/A3: CALL OUT THE DOUBLE 2X SIZE. 4. DETAIL 7/A3: THE NEW 4X6 CALLS OUT FOR A CONNECTION TO THE 'BOTTOM CHORD OF JOISTS'. IT IS ACTUALLY CONNECTING TO THE NEW DOUBLE 2X. VERIFY. 5. DETAIL 7/A3: A NOTE IN THE 4X6 INDICATES A 200# CAPACITY. REVISE THAT ALLOWABLE LOAD. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |