Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM07696
Parcel: 14026023A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07696
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET D-1; DEMOLITION PLAN, SHEET A-1; FLOOR PLAN, SHEET A-2; CEILING PLAN:
1. THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE ALL DRAWINGS WITH THIS NONCOMPLIANCE AND RESUBMIT.
SHEET A-1:
2. NOTE 3, VERIFY THAT THIS DOES NOT REQUIRE A STRUCTURAL REVIEW OF THE EXISTING ROOF? IF SO, THEN REVISE AND PROVIDE STRUCTURAL CALCULATIONS.
SHEET A3:
4. At Detail 11, the maximum counter height for an accessible counter is 36" as per ICC A117.1, Section 404.
5. At detail 15:
a. Provide structural calculations for the 8' high chain link fence
b. Provide Certification of the special inspector for epoxy anchors
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
END OF COMMENTS
12/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
12/18/2012 ROBERT SHERRY WATER REVIEW Approved
12/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/18/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/21/2012 GERRY KOZIOL WWM REVIEW Passed