Permit Number: T12CM07696
Parcel: 14026023A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07696
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
12/05/2012 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/05/2012 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/05/2012 CAGUILA1 WATER REVIEW Needs Review
12/05/2012 CAGUILA1 BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D-1; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PARTITION NOTES.
2. SHEET A-1; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PARTITION AND ROOM NOTES.
3. SHEET A-1; FLOOR PLAN KEYNOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. DOES THIS REQUIRE A STRUCTURAL REVIEW OF THE EXISTING ROOF? REVISE.
4. SHEET A-2; CEILING PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PARTITION NOTES.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/05/2012 CAGUILA1 WWM REVIEW Needs Review
12/05/2012 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/05/2012 PAUL MACHADO ENGINEERING REVIEW Approved
12/05/2012 CAGUILA1 FIRE REVIEW Needs Review
12/05/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/05/2012 ERIC NEWCOMB ADA REVIEW Passed