Permit Number: T12CM07502
Parcel: 12205003C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07502
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2012 STEVE SHIELDS ZONING REVIEW Approved
11/28/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/28/2012 ROBERT SHERRY WATER REVIEW Approved
11/28/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; FLOOR PLAN KEYNOTES: NOTE 15 CAN NOT BE APPROVED AT THIS TIME UNTIL A WAIVER IS APPROVED BY THE BUILDING OFFICIAL.
2. SHEET A1.0; DETAILS 1 AND 2: PROVIDE THE QUANTITIY AND SIZE OF CONNECTORS FOR BRACING TO THE STRUCTURE ABOVE AND TO THE TOP OF THE WALL.
3. SHEET A1.0: PROVIDE THE SIZE AND SPACING OF THE WALL STUDS.
11/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the modifications to the existing lavatory. Keynote 4/MP1.0 indicates that the existing water heater associated with the lavatory is to remain but Keynote 2/MP1.0 calls for a new 1/2" hot water supply for the same lavatory. Show how this is to be done.
2. Show how the temperature of the hot water supply to the lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
11/28/2012 ERIC NEWCOMB ADA REVIEW Passed
11/28/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/29/2012 SPOWELL1 WWM REVIEW Needs Review
11/29/2012 SPOWELL1 FIRE REVIEW Needs Review
11/29/2012 SPOWELL1 ENGINEERING REVIEW Needs Review