Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM07440
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/28/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Unless the submitted Private Utility Plan, sheet 16 of 28, is an older version, the civil plan still shows a 1-1/2" water service pipe whereas the plumbing drawing P-1.1 calls for a 2" water service pipe. [Original comment: Coordinate the size of the water service pipe shown on the plumbing plans with the civil utility plans.] 2. The overflow scupper detail, 10/A-2.1 calls for the overflow scuppers to be 16" wide by 8" high; coordinate the scupper dimensions with the calculations shown on sheet P-1.1. [Original comment: Provide hydraulic calculations to determine the required size of the roof scuppers (rectangular weirs). Reference: Sections 1106 and 1107.3, IPC 2006.] 3. "Ready access" is defined in the 2006 IPC as requiring the equipment or fixture to "…be directly reached requiring the removal or movement of any panel, door, or similar obstruction…"; the wall register shown in detail 3/P-1.1 is an obstruction that requires removal in order to access the indirect waste receptor. [Original comment: Clarify how the installation of the wall drain box detail (3/P1.1) complies with the ready access requirement of Section 802.3, IPC 2006. Reference: Section 202, "Ready Access", IPC 2006.] |
| 01/29/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that the supply air is exhausted even when the lights are turned off during the operating hours of the building. [Original comment: Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.] |
| 01/31/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/13/2013 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: CVS PHARMACY - DP12-0183 2: 4" HCS TO 10" PUBLIC SEWER 3: PROPRTY SPLIT, NEED TO CLARIFY/SHOW ON DRAWINGS SIZE, LOCATION AND NUMBER OF ALL WATER METERS REMOVED FOR SEWER CONNECTION FEE CREDIT EVALUATION 4: NEED DP APPROVAL FROM WW - CHAD AMATEAU 740-6547 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/13/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |