Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM07440
Parcel: 134234110

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM07440
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2012 MARTIN BROWN FIRE REVIEW Approved
11/29/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details for the 19 gallon water heater mounted on the wall.
SHEET S2.2
2. At detail 1/S2.2: Drawings show 18K4/14K3/18K4 and 14K1 joists sequenced from South to North. The calcs show Type I 18K5, Type II 14K3, Type I 18K5 and Type III 14K1. Please reconcile.
3. At the South end of the stair well opening, between cols 3 and 4/A, the drawings show a continous W14x22 , it looks like the calcs calls for a W12x19 and a new column. Please reconcile.
4. The steel beam on the 45 degree angle at the front entrance is shown on the drawings as a W12x9. The Calcs calls for a W18x40. Please reconcile.
5. B9 shown in the beam schedule is not shown in the calcs.
6. Calcs reference column E9-4.4. There is no column shown at this grid intersection on the drawings.
7. Footing CF3 shown in the calcs is not included in the beam schedule on sheet S1.1.
8. CF4A and CF45 shown in the beam schedules is not called for in the calcs. Please reconcile.
END OF REVIEW
12/07/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the size of the water service pipe shown on the plumbing plans with the civil utility plans.
2. Show that the back-to-back installation of water closets complies with the requirements of Section 706.3, IPC 2006.
3. Provide hydraulic calculations to determine the required size of the roof scuppers (rectangular weirs). Reference: Sections 1106 and 1107.3, IPC 2006.
4. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006.
5. Clarify how the installation of the wall drain box detail (3/P1.1) complies with the ready access requirement of Section 802.3, IPC 2006. Reference: Section 202, "Ready Access", IPC 2006.
12/07/2012 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies protecting the municipal water distribution system from the building water service are required to be installed in locations accessible to Tucson Water. Typically, the reduced pressure backflow prevention assemblies are installed adjacent to the water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
12/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Clarify how the projection factors were calculated for the windows located on the north and west walls. Reference: Section 104.2, IECC 2006.
3. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
12/10/2012 TERRY STEVENS ZONING REVIEW Approved
12/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied t12CM07440
6310 E Broadway Bl
New CVS Store

1. Provide a calculation showing compliance with 2012 City of Tucson Outdoor Lighting Ordinance # 10963, which can be found on the City's Web Page by going to Departments, Development Services , Codes, then Building Codes, The calculation is per area and option, includes Lumen count of all outdoor lighting, site and building inclusive.Required by C of Tucson Submittal Requirements. Should be shown on Sheet SE-1.2.
2. Sheet SE-1.1, show a detail of the service including clearance requirements, per 2005 NEC 110.26.
3. Provide in electrical sheets, a floor plan detail showing the lay out all electrical panels on mezzanine level. Required per C of T Sumittal Requirements.
4. Regarding fault current considerations on Sheet E-3.1, these are considered critical, if the location of the utility is not clearly known or if it may be changed, the full value of the fault current at the transformer should be used. Also engineer must determine the type of series rated system to be used such as 36/10K or other, indicate on plan.

Ray T Majuta
Electrical Plan Review,
PDSD, C of Tuc
12/17/2012
Ray.Majuta@tucsonaz.gov
12/18/2012 CPIERCE1 WWM REVIEW Denied 1: CVS PHARMACY - DP12-0183
2: 4" HCS TO 10" PUBLIC SEWER
3: NEED TO SHOW SIZE, LOCATION AND NUMBER OF ALL NEW WATER METERS ON BUILDING DRAWINGS FOR SEWER CONNECTION FEE CALCULATION
4: NEED TO SHOW SIZE, LOCATION AND NUMBER OF ALL WATER METERS REMOVED FOR SEWER CONNECTION FEE CREDIT EVALUATION
5: NEED DP APPROVAL FROM WASTEWATER - CHAD AMATEAU 740-6547

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2012 CPIERCE1 OUT TO CUSTOMER Completed
12/19/2012 CPIERCE1 REJECT SHELF Completed