Permit Number: T12CM07328
Parcel: 11454057F

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM07328
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2012 RONALD BROWN ZONING HC REVIEW Passed
12/19/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/20/2012 STEVE SHIELDS ZONING REVIEW Approved
12/26/2012 GERRY KOZIOL WWM REVIEW Denied 1.WALGREENS-DPR-0137
2. NEED CIVIL DRAWINGS IN BUILDING SET SHWNG LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
3. NEED TO SHOW THE SIZE,LOCATION & WATER METER NUMBER OF ALL WATER METERS ON THE PROPERTY FOR WASTEWATER SEWER CONNECTION FEE EVALUATION (IF EXISTING NEED VERIFICATION OF USER FEES)
12/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved; a revised civil plan was not submitted. [Original comment: Coordinate the civil site drawing (C-400) with the plumbing plan. The civil plan shows a 2" water service line entering the building near column D-4 and an existing 1-1/2" water meter located on the east property line; the reduced pressure backflow preventers for water service and for irrigation service are located adjacent to the water meter. Reference: Section 106.3.1, IPC 2006.]
12/28/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2013 CPIERCE1 REJECT SHELF Completed
12/31/2012 CPIERCE1 APPROVAL SHELF Completed