Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/26/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A410
1. At details 10 and 11: The accessible urnial stall is to be 3'-0" as per ICC A117.1, Section 605 and 305.
SHEET P610
2. Detail 6: Provide structural calculations and details for the 40 gallon (320# + tank) water heater. Generic bracket details are not acceptable.
END OF REVIEW
11/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the civil site drawing (C-400) with the plumbing plan. The civil plan shows a 2" water service line entering the building near column D-4 and an existing 1-1/2" water meter located on the east property line; the reduced pressure backflow preventers for water service and for irrigation service are located adjacent to the water meter. Reference: Section 106.3.1, IPC 2006.
2. Revise or remove detail 3/P-610. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (See civil drawing C-400). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
3. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure (no details were found in the architectural or structural drawings). Clarify the tag for the water heater; it is GWH-1 on sheet P-111 and EWH-1 on sheet P-610. Reference: Sections 106.3.1 and 301.2, IPC 2006.
4. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070 (the specified thermostatic mixing valve is listed as conforming to ASSE 1017). Reference: Section 416.5, IPC 2006.
5. Provide an approved anti-siphon device (e.g. vacuum relief valve) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2006.
6. Show how the roof drains and the overflow roof drains are to be terminated. Reference: Sections 1101.8 and 1107.2, IPC 2006.
11/29/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Walgreens @ 8980 E. Tanque Verde Road
T12CM07328
Building Plan (1st Review)

TRANSMITTAL DATE: November 29, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans and it appears that the proposed plans meet the requirement of the development package. Zoning will approve and stamp the building plans once all other PDSD agencies have approved the building plan.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
11/29/2012 ROBERT SHERRY WATER REVIEW Approved
11/30/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Use the exterior design criteria for Pima County, <4,000 feet of elevation as stated in Section 302.2, IECC 2006, as amended by the City of Tucson rather than the exterior design criteria for Davis-Monthan Air Force Base.
3. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
4. Revise details 1, 2, and 3/M-520 for legibility. The backgrounds and notes don't appear on the details. Reference: Section 106.3.1, IMC 2006.
5. Show the size, routing, and termination of the condensate drains for the freezer and cooler evaporators. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.
12/03/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/04/2012 GERRY KOZIOL WWM REVIEW Denied 1: WALGREENS - DPR- 0137
2: NEED CIVIL DRAWINGS IN BUILDING SET SHOWING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
3: NEED TO SHOW THE SIZE, LOCATION & WATER METER NUMBER OF ALL WATER METERS ON THE PROPERTY FOR WASTEWATER SEWER CONNECTION FEE EVALUATION (IF EXISTING NEED VERIFICATION OF USER FEES PAID)

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2012 CPIERCE1 REJECT SHELF Completed