Permit Number: T12CM06399
Parcel: 14111029B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06399
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a cleanout for the kitchen sink. [Original comment: Provide cleanouts for the upper terminals of the building drain and its horizontal branches. Reference: Section 707.4, UPC 2006.]
01/30/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the projection factors for the windows; they do not all have the same value (e.g. the windows under the porch have a pf = 1.18, the south windows have a pf = 0.24, and the remaining windows have a vanishingly small projection factor). [Original comment: Revise the energy code compliance calculations for the building envelope. Coordinate the details on the drawings with the components shown on the energy compliance calculations. The information on the drawings shall, as a minimum, include U-factors and the SHGC of the fenestration components. Verify that all of the windows have the same projection factor shown on the calculations. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
01/30/2013 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2013 CPIERCE1 REJECT SHELF Completed