Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06399
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/30/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a cleanout for the kitchen sink. [Original comment: Provide cleanouts for the upper terminals of the building drain and its horizontal branches. Reference: Section 707.4, UPC 2006.] |
| 01/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the projection factors for the windows; they do not all have the same value (e.g. the windows under the porch have a pf = 1.18, the south windows have a pf = 0.24, and the remaining windows have a vanishingly small projection factor). [Original comment: Revise the energy code compliance calculations for the building envelope. Coordinate the details on the drawings with the components shown on the energy compliance calculations. The information on the drawings shall, as a minimum, include U-factors and the SHGC of the fenestration components. Verify that all of the windows have the same projection factor shown on the calculations. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.] |
| 01/30/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2013 | CPIERCE1 | REJECT SHELF | Completed |