Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM05861
Parcel: 12001001M

Address:
1335 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05861
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Revise the energy code analysis for the building envelope, using Pima County < 4,000 feet, not Oro Valley. Coordinate the building components used in the analysis (e.g. continuous roof insulation) with those shown on the drawing. Reference: Sections 302.2 and 502, IECC 2006, as amended by the City of Tucson.
10/31/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/01/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM05861
1335 W Ajo
Dollar General

Sent E-mail today today to Mr Jack Cronell ,PolyPhase Eng,
concerning the response letter dated Oct 26,2012.The letter
had comments on allowing the 400 amp service to be allowed which would feed a 398 amp load. After consideration and in talking to other Plans Examiners including some from other jurisdictions, it was decided to request a larger service to feed the 398 amp load. We research three other Dollar
General Buildings in Tucson and found each to be fed with 50 amps or more to each. I feel that the building being new requires a larger ampacity at the service in order to provide for growth. The NEC , Article 90 Section B indicates that an installation be adequate for good service or future expansion of electrical use. This service is too close for it's calculation.



Ray T Majuta
Electrical Plans Examiner
PDSD, C of Tuc
11/2/2012
Ray.Majuta@tucsonaz.gov
11/07/2012 STEVE SHIELDS ZONING REVIEW Approved
11/14/2012 GERRY KOZIOL WWM REVIEW Approved