Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM05861
Parcel: 12001001M

Address:
1335 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM05861
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond Plan notes were changed to indicate that an automatic fire sprinkler system will be installed.
1. Plans and separate permits are required for the fire sprinkler underground, fire sprinkler aboveground and fire alarm system.
10/02/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05861
1335 W Ajo WY
Dollar General
Sheet 401:
Concerning the capacity of the service and the total load calculation, the calculation does not appear to have 125%
added for the largest motor, per 2005 NEC 220 Part Three,
220.50 for motor loads.
Please explain the "Misc" load figured in at 24,754 va.
The 398 amp load on the 400 amp service appears to close,
see 2005 NEC 90.1.B, Adequacy and also FPN.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
10/12/2012
Ray.Majuta@tucsonaz.gov
10/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the size of the water meter serving the building with the civil plans which show a 1" water meter being installed. In addition, Tucson Water limits the use of ¾" water meters to a demand of 22.5 GPM.
2. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2006.
3. If the use of PEX tubing is to be allowed for the waster distribution system, provide a pipe sizing chart to guide the contractor; for example, based on the chart shown on sheet P-102, 3 GPM in a ½" Type L copper pipe has a pressure drop of 9 PSI/100 Feet but with the same flow, ½" PEX has a pressure drop of 12.5 PSI/100 Feet. Reference: Section 604.1, IPC 2006.
4. Provide for sterilization and testing of the domestic water system per Section 610, IPC 2006.
5. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown on P-102. Reference: Sections 708.3.5 and 708.5, IPC 2006.
6. Provide protection of the trap seals for all floor drains subject to infrequent use. Elastomeric devices designed to physically seal the trap and prevent loss of the water seal (e.g. Pro-vent Trap Guards, Sure Seal Trap Sealers, et al) are not approved for use in the City of Tucson. Reference: Sections 706.2 and 1002.4, IPC 2006.
10/12/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (e.g. the exhaust fans shall operate even when the lights are off if the supply air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006.
3. Revise the energy code analysis for the building envelope, using Pima County < 4,000 feet, not Oro Valley. Coordinate the building components used in the analysis (e.g. continuous roof insulation) with those shown on the drawing. Reference: Sections 302.2 and 502, IECC 2006, as amended by the City of Tucson.
10/12/2012 ROBERT SHERRY WATER REVIEW Approved
10/16/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Dollar General @ Ajo and Pandora
T12CM05861
Building Plan (1st Review)

TRANSMITTAL DATE: October 16, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until a development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/24/2012 GERRY KOZIOL WWM REVIEW Denied 1: DOLLAR GENERAL
2: CONNECTING TO 1" WATER METER
3: NEED DP REVIEW & APPROVAL PER PCRWRD/KRISTIN GREENE
10/22/12

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2012 CINDY AGUILAR REJECT SHELF Completed