Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM05861
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/01/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Plan notes were changed to indicate that an automatic fire sprinkler system will be installed. 1. Plans and separate permits are required for the fire sprinkler underground, fire sprinkler aboveground and fire alarm system. |
10/02/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/10/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05861 1335 W Ajo WY Dollar General Sheet 401: Concerning the capacity of the service and the total load calculation, the calculation does not appear to have 125% added for the largest motor, per 2005 NEC 220 Part Three, 220.50 for motor loads. Please explain the "Misc" load figured in at 24,754 va. The 398 amp load on the 400 amp service appears to close, see 2005 NEC 90.1.B, Adequacy and also FPN. Ray T Majuta Elect Plan Review PDSD, C of Tuc 10/12/2012 Ray.Majuta@tucsonaz.gov |
10/12/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the size of the water meter serving the building with the civil plans which show a 1" water meter being installed. In addition, Tucson Water limits the use of ¾" water meters to a demand of 22.5 GPM. 2. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2006. 3. If the use of PEX tubing is to be allowed for the waster distribution system, provide a pipe sizing chart to guide the contractor; for example, based on the chart shown on sheet P-102, 3 GPM in a ½" Type L copper pipe has a pressure drop of 9 PSI/100 Feet but with the same flow, ½" PEX has a pressure drop of 12.5 PSI/100 Feet. Reference: Section 604.1, IPC 2006. 4. Provide for sterilization and testing of the domestic water system per Section 610, IPC 2006. 5. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown on P-102. Reference: Sections 708.3.5 and 708.5, IPC 2006. 6. Provide protection of the trap seals for all floor drains subject to infrequent use. Elastomeric devices designed to physically seal the trap and prevent loss of the water seal (e.g. Pro-vent Trap Guards, Sure Seal Trap Sealers, et al) are not approved for use in the City of Tucson. Reference: Sections 706.2 and 1002.4, IPC 2006. |
10/12/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. 2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (e.g. the exhaust fans shall operate even when the lights are off if the supply air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006. 3. Revise the energy code analysis for the building envelope, using Pima County < 4,000 feet, not Oro Valley. Coordinate the building components used in the analysis (e.g. continuous roof insulation) with those shown on the drawing. Reference: Sections 302.2 and 502, IECC 2006, as amended by the City of Tucson. |
10/12/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/16/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Dollar General @ Ajo and Pandora T12CM05861 Building Plan (1st Review) TRANSMITTAL DATE: October 16, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until a development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
10/24/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: DOLLAR GENERAL 2: CONNECTING TO 1" WATER METER 3: NEED DP REVIEW & APPROVAL PER PCRWRD/KRISTIN GREENE 10/22/12 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/30/2012 | CINDY AGUILAR | REJECT SHELF | Completed |