Review Details: REVISION - - 1ST

Permit Number - T12CM05824
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM05824
Photovoltaic Addition

1. The plans must be sealed by a registered applicant, per City of Tucson Commercial Submittal Requirements. Remove
"Not for Construction" statement on plans.
2.The overcurrent protection on the Main disconnect to the 300kv Transformer to comply with 2005 NEC 240.4.C.
3. Transformer overcurrent protection to comply with 2005 NEC 450.3.B.
4. Is the Inverter overcurrent protection device be part of the overcurrent protection required for the Transformer ?
5. Tap rule regarding the secondary feeders of the 300kva transformer , indicate how 240.21 is complied with.
6. Provide information on fault current values and new equipment per 2005 NEC 110.9 .
7. Indicate transformer to be outdoor rated.
8. Provide a specification sheet on new inverter to be used.
9. How are the three sets of 4/500 mcm conductors to be landed on the existing 2000 a SES E, which compartment, how will the conductors enter the SES, will the conductors have sufficient room to terminate, is the bus on the switchgear pre drilled and approved for new conductor landings ?

Ray T Majuta
Elect Plan review,
DSD, City of Tucson,
3/8/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2013 CPIERCE1 APPROVAL SHELF Completed
03/21/2013 CPIERCE1 OUT TO CUSTOMER Completed