Permit Number: T12CM05824
Parcel: 11516019S

Address:
1365 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05824
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05824

1. Previous review (10-25-12) requested specification sheets for the modules, inverters and combiner boxes. Only a specification sheet was submitted for the modules and does not match the the model number with the one on the plans.
The specification sheet indicates an Eoplly 156P-245, the plan shows a Candian Solar CS6P-245. The spec numbers for each is different, and values different.
Specification sheets were not submitted for the inverters or the combiner boxes. These specification sheets must come from the manufacture and provide all specifications and show an approved listing.
The calculations must then co-inside with the values from the spec sheets.
The calculation sheet submitted with the module spec sheet shows two 135 KW inverters( Satcon Powergate Plus
PVI 135), the plan sheet E2.0 shows three Solectria Inverters, 2-95 KW and one 85 KW.
Please review and address each comment.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
11/27/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2012 SHANAE POWELL REJECT SHELF Completed