Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM05572
Parcel: 13819045B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05572
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide partial toilet plans and interior elevations for all the toilet rooms showing all accessible requirements: dimensions (vertical and horizontal), clearances, accessories, signage, fixtures and required finishes as required by ICC A117.1, 2003 Edition.
2. Please provide individual partial plans, sections and elevations for all the different types of stairs (3 sets) showing all dimensions, risers and treads, handrails and landings. Please provide handrail elavations.
SHEET A1.2
3. The stage ramp is non-compliant as per the 2006 IBC, Section 405.7; 5' landings and handrails.
a. Please provide an elevation of the handrails as per ICC A117.1, Section 505.10.1.
SHEET A2.0
4. Show section through wrought iron railing at the choir loft and structural calculations for requirements os the 2006 IBC, Section 1607.7.1.
a. Guard rails are to be a minimum of 3'-6" high. Please revise your notes calling for 36".
SHEET A3.0
5. The City of Tucson actual lettering size for construction drawings is 3/32" upper and lower case, actual not font size.
Please revise this sheet and resubmit.
END OF REVIEW
09/11/2012 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05572

1. Sheet E-8, the feeders from the 1000 amp overcurrent device at new SES to existing service are required per 240.4.B. to be equal to or above in ampacity than the 1000 amp overcurrent device.

Ray T Majuta
PDSD, C of Tuc
9/18/2012
520-837-4988
09/25/2012 GERRY KOZIOL WWM REVIEW Denied 1: ST MONICA ROMAN CATHOLIC PARISH- SANCTUARY REMODEL
2: EXISTING 2" WATER METER PER UTILITY PLAN C2- CONNECTING TO EXISTING ON-SITE PRIVATE SEWER
3: NEED WATER METER CLARIFICATION - NEED VERIFICATION FROM WATER SUPPLIER- NEED SIZE, LOCATION, NUMBER & DATE OF INSTALLATION FOR ALL WATER METERS ON THE PROPERTY WITH PLUMBING FIXTURES SERVED FOR SEWER CONNECTION FEE CALCULATION
4: NEED CAPACITY EVALUATION -(ADDED 72FU'S) - KURT STEMM - 740-6607
09/26/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: St. Monica Roman Catholic Parish
T12CM05572
Building Plan (1st Review)

TRANSMITTAL DATE: September 26, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until a development package has been submitted and approved for the proposed expanison.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/03/2012 ROBERT SHERRY WATER REVIEW Approved
10/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the connection of the drain for lavatory P-1A to water closet P-2A as shown in detail A/P2.0; is the lavatory drain connecting above or below the trap arm for the water closet?
2. Clarify the number of 4" cleanouts shown in detail B/P2.0 for the water closets; the note says 4" WCO (TYP. 6) but this appears to conflict with the other notes in the detail that indicate that the drains for five of water closets are 3" in size.
3. Clarify the note in the plumbing schedule for the mop sink, P6, which says "vent underground".
4. Show that the connection of the T&P relief discharge pipe to the water heater pan drain (WH-1) does not violate the installation instructions for the T&P valve. Reference: Sections 310.4 and 608.5, UPC 2226.
5. Verify that the building sewer on the west end of the sanctuary connects to the private sewer such that the rim elevation of the upstream manhole or cleanout is 12" below the first floor elevation of the sanctuary. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.
10/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.
2. Provide note 5, which is referenced in the exhaust fan schedule.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
10/15/2012 CINDY AGUILAR REJECT SHELF Completed