Permit Number: T12CM04972
Parcel: 125120810

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM04972
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Detail 2A/A2 does not represent a 1 hour rated elevator shaft assy. The two layers of 5/8" "X" rated gypsum board must go all the way to the bottom of the deck and be fire calked at the top and bottom plates similar to the deleted detail 4/A2.
a. It also does not reflect a 1 hour ceiling for the elevator machine room. It must have two layers gypsum board, 1 on either side if the framing studs, not just one or have all the 2 hour gypsum board partitions go to bottom of deck and insure the deck has a minimum of 1 hour rating.
END OF REVIEW
10/04/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/04/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/04/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2012 CPIERCE1 APPROVAL SHELF Completed
10/10/2012 CPIERCE1 OUT TO CUSTOMER Completed