Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM04972
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Detail 2A/A2 does not represent a 1 hour rated elevator shaft assy. The two layers of 5/8" "X" rated gypsum board must go all the way to the bottom of the deck and be fire calked at the top and bottom plates similar to the deleted detail 4/A2. a. It also does not reflect a 1 hour ceiling for the elevator machine room. It must have two layers gypsum board, 1 on either side if the framing studs, not just one or have all the 2 hour gypsum board partitions go to bottom of deck and insure the deck has a minimum of 1 hour rating. END OF REVIEW |
10/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/04/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/04/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/10/2012 | CPIERCE1 | APPROVAL SHELF | Completed |
10/10/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |